3. Regeneration Type (Display Code 7)
Use this program step, identified by the number 7 in the first digit of the display, to set the Regeneration Type.
There are 4 possible settings:
Default =
Meter Delayed Regeneration [ 7 - - 3 ]
Available Regeneration Types and their Dependencies
—Use the Set Up and Set Down buttons to adjust this value.
Press the Extra Cycle button to proceed to the next step.
Time Clock Delayed Setting: [ 7 - - 1 ]
The control regenerates on the days set in program step #7, at the Regeneration Time
set in program step #6.
Meter Immediate Setting: [ 7 - - 2 ]
The control regenerates immediately when the available volume of softened water drops to 0.
Meter Delayed Setting: [ 7 - - 3 ]
The control regenerates on the day the available volume of softened water drops to less than the reserve
volume. Regeneration starts at the Regeneration Time set in program step #6.
Meter Delayed - Variable Brining Setting: [ 7 - - 4 ]
The control regenerates on the day that the available volume of softened water drops to or below the reserve
volume. Regeneration starts at the Regeneration Time set in program step #6. With the variable brining
option activated, the time setting for Cycle 1 is automatically calculated based on the volume of treated water
at the time of regeneration. Cycle time 1 will not exceed the original time setting and is never less than one (1)
minute.
Piston / CAM Type Regeneration Types Available
dF [ 7 - - 1 ], [ 7 - - 2 ], [ 7 - - 3 ]
dFFF [ 7 - - 1 ], [ 7 - - 3 ], [ 7 - - 4 ]
Fltr [ 7 - - 1 ]
Default
dF [ 7 - - 3 ]